Sign In | Join Free | My himfr.com
Home > Pepperl Fuchs Safety Barrier >

2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode

Achievers Automation Limited
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap 2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode from wholesalers
     
    Buy cheap 2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode from wholesalers
    • Buy cheap 2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode from wholesalers
    • Buy cheap 2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode from wholesalers
    • Buy cheap 2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode from wholesalers
    • Buy cheap 2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode from wholesalers

    2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode

    Ask Lasest Price
    Brand Name : PEPPERL FUCHS
    Model Number : KFD2-UT2-1
    Price : Negotiable
    Payment Terms : T/T
    Supply Ability : 100pcs per month
    Delivery Time : Negotiable
    • Product Details
    • Company Profile

    2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode

    PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink or source mode


    General specifications
    Signal type Analog input
    Functional safety related parameters
    Safety Integrity Level (SIL) SIL 2
    Supply
    Connection terminals 14+, 15- or power feed module/Power Rail
    Rated voltage 20 ... 30 V DC
    Ripple within the supply tolerance
    Power dissipation ≤ 0.98 W
    Power consumption max. 0.98 W
    Interface
    Programming interface programming socket
    Input
    Connection side field side
    Connection terminals 1, 2, 3, 4
    RTD type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
    type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
    type Cu10, Cu50, Cu100 (P50353-92)
    type Ni100 (DIN 43760)
    Measuring current approx. 200 µA with RTD
    Types of measuring 2-, 3-, 4-wire connection
    Lead resistance max. 50 Ω per line
    Measurement loop monitoring sensor breakage, sensor short-circuit
    Thermocouples type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
    type L (DIN 43710: 1985)
    type TXK, TXKH, TXA (P8.585-2001)
    Cold junction compensation external and internal
    Measurement loop monitoring sensor breakage
    Potentiometer 0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
    Voltage selectable within the range -100 ... 100 mV
    Input resistance ≥ 1 MΩ (-100 ... 100 mV)
    Output
    Connection side control side
    Connection output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)
    Output Analog current output
    Current range 0 ... 20 mA or 4 ... 20 mA
    Fault signal downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
    Source load 0 ... 550 Ω
    open-circuit voltage ≤ 18 V
    Sink Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
    series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
    The maximum value of the resistance is (V - 5)/0.0215 Ω.
    Transfer characteristics
    Deviation
    After calibration Pt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection))
    thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1 K (1.2 K for types R and S)) , includes ± 0.8 K fault of the cold junction compensation (CJC)
    mV: ± (50 µV + 0.1 % of span)
    potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes faults due to lead resistance))
    Influence of ambient temperature Pt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*)
    thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*)), influence of cold junction compensation (CJC) included
    mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*)
    potentiometer: ± 0.006 % of span/K ΔTamb*)
    *) ΔTamb = ambient temperature change referenced to 23 °C (296 K)
    Influence of supply voltage < 0.01 % of span
    Influence of load ≤ 0.001 % of output value per 100 Ω
    Reaction time worst case value (sensor breakage and/or sensor short circuit detection enabled)
    mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s


    2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode

    Quality 2 4 Wire PEPPERL FUCHS Universal Temperature Converter KFD2-UT2-1 Sink Source Mode for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Achievers Automation Limited
    *Subject:
    *Message:
    Characters Remaining: (0/3000)